Products catalog

  • ADA100 ECU 4 Zone emergency call control unit

    Code: 03471
    8300 € VAT excl.
    Out of stock.
    Contact us
    In stock: 0 pcs
  • Emergency call control unit designed to manage alarm activation, visual LED status indication, internal buzzer alerts, field device inputs, field device outputs, and battery backup for assistance and emergency call systems.

    Main Features:

    • Emergency call unit for managing alarm and assistance call systems
    • 230 VAC mains power input with 12 VDC battery backup support
    • Green mains LED indicates mains power status
    • Battery backup LED pulse every 5 seconds
    • Battery saver LED pulse every 20 seconds
    • Red alarm LEDs for Zone 1, Zone 2, Zone 3, and Zone 4 alarm indication
    • Internal PCB-mounted piezo buzzer for audible alarm signalling
    • Buzzer provides 1 kHz tone with 1 Hz pulse during alarm activation
    • Sound mute function when the system is normal
    • Supports field device input monitoring with open circuit and short circuit detection
    • Field device output with 12 VDC sounder supply
    • Battery charging voltage of 13.8 VDC
    • Deep discharge battery protection below 10.5 VDC
    • Fire-retardant polycarbonate front cover and back box

    Specifications:

    • Model: ADA100 ECU
    • Mains input voltage: 230 VAC, 50 Hz / 60 Hz
    • DC input voltage: 12 VDC battery
    • Quiescent standby current: 3 mA DC, buzzer muted
    • Maximum overall supply current: 250 mA DC
    • Maximum current during alarm: 30 mA DC
    • Mains LED: green, constant when mains is present
    • Alarm LEDs: red, slow flashing at 1 Hz during alarm activation
    • Internal buzzer type: PCB-mounted piezo
    • Buzzer current: 5 mA maximum
    • Buzzer frequency: 1 kHz tone
    • Alarm buzzer pulse: 1 Hz pulse
    • Battery saver buzzer: beep every 20 seconds
    • Number of field device input zone circuits: 1
    • Field device input voltage: 12 VDC ±10%
    • Detection supply maximum current: 30 mA
    • Short circuit detection: >30 mA
    • Open circuit monitoring: <1.5 mA
    • Number of field device output zone circuits: 1
    • Field device output voltage: 12 VDC ±10%
    • Sounder supply maximum current: 200 mA
    • Battery charging voltage: 13.8 VDC
    • Deep discharge protection: less than 10.5 VDC
    • Fuse F1 auxiliary: 500 mA anti-surge 20 mm glass
    • Fuse F2 battery: 500 mA anti-surge 20 mm glass
    • Housing front cover: fire-retardant polycarbonate
    • Housing back box: fire-retardant polycarbonate

    Notes:

    • Designed for use with compatible ADA100 call, reset, and indicator devices
    • Installation should be carried out according to emergency call system wiring and safety requirements