GFE MAM Y
Code: 5852251 €In stock.
4 pcs - Vilnius
4 pcs - Kaunas
0 pcs - Central WarehouseIn stock: 9 pcs-
Global Fire Equipment MAM Detector Interface Module
Compact manually-addressed module from the MAM series, designed to enable integration of conventional detectors into an addressable fire alarm loop system.
Main Features:
- Loop supply voltage: 17 V to 30 V DC
- Quiescent loop current: approx. 1.1 mA
- Alarm loop current: approx. 12 mA
- Address range: 1-125 for detectors/MCP/I/O devices; 94-125 reserved for sounder/beacon devices
- Compact dimensions: 48 mm × 24 mm × 9 mm
- Latching 8-way DIP switch for manual address setting and configuration of device type (detector, MCP, input, output, etc.)
- Supports white-indicator version (for detector module applications) along with coloured housings for other module types
Notes:
- Ensure the connected conventional detector is compatible with the module’s interface specifications.
- Include the module’s quiescent and alarm current in loop load calculations to avoid overload.
- Connect “IN” and “OUT” loop terminals correctly and maintain proper polarity as specified in the installation manual.
- For reliable system integration and compliance with applicable fire-detection standards, professional installation is recommended.