Products catalog

  • GFE ZMU

    Code: 1823
    5083 € VAT excl.
    Out of stock.
    Contact us
    In stock: 0 pcs
  • Global Fire Equipment QUAD-ZMU Addressable Quad Zone Monitoring Unit

    A fully monitored addressable module allowing connection of up to four individually addressed conventional detection zones into the addressable loop of a GFE fire alarm control system.

    Main Features:

    • Loop supply voltage: 20 V to 30 V DC; loop current approx. 1.6 mA
    • Requires external 24 V DC power supply for conventional zones; zone output and loop are optically isolated
    • Supports active end-of-line (EOL) monitoring, enabling detector removal supervision
    • Monitors open-circuit, short-circuit and fire conditions on each connected conventional zone
    • LED indication for each zone: red = fire, yellow = fault, green = 24 V supply present
    • Zone programming supports up to four zones (models labelled 1Z, 2Z, 3Z, 4Z)
    • Maximum cable size up to 2.5 mm²; operating temperature –10 °C to +50 °C; up to 95% RH non-condensing
    • Dimensions: 150 × 90 × 32 mm; Weight approx. 220 g
    • Complies with EN54-18 for interface modules

    Notes:

    • The module occupies multiple consecutive loop addresses depending on the number of zones configured.
    • Ensure correct selection of EOL type (active vs resistive) and correct wiring of each conventional zone.
    • The external 24 V supply for the conventional zone devices must be adequate for the connected devices and supervision circuitry.
    • Professional installation is recommended to ensure compliance with system design, wiring integrity and relevant standards.