MAM Y, Automatic siren control device (LSCM 1)
Code: 42042251 €In stock.
5 pcs - Vilnius
4 pcs - Kaunas
0 pcs - Central WarehouseIn stock: 10 pcs-
Global Fire Equipment MAM LSC Output Manually Addressed Module
Manually addressed interface module allowing connection and addressing of conventional sounders/beacons within an addressable fire alarm loop, enabling retrofit of conventional components into an addressable system.
Main Features:
- Loop-powered: 17 V to 30 V DC
- Quiescent loop current: ~1.1 mA
- Alarm loop current: ~12 mA when output active
- Address range: 1-125 for detectors/MCP/I/O or 94-125 for sounder/beacon devices
- Max cable size: up to 2.5 mm² conductors
- Operating temperature: ?10 °C to +50 °C; Maximum humidity: 95 % RH non-condensing
- Compact dimensions: 48 mm × 24 mm × 12 mm; Weight: ~18 g
- 8-way DIP switch for address and mode configuration (e.g., sounder vs beacon behaviour)
Notes:
- Ensure loop wiring meets specification and that module quiescent + alarm currents are included in loop load calculations.
- Switching between sounder and beacon modes can be achieved via DIP switch settings according to installation requirements.
- When used for retrofit, ensure conventional sounder/beacon connected to module is compatible with its output behaviour and that the system’s panel supports the module.
- Professional installation is recommended to ensure reliable integration and full system compliance.